Catalog
|
HV glass suspension insulator U 40BP
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
Designation
|
IEC 305
|
U40ÂÐ
|
|
Mechanical failing load
|
kN
|
40
|
|
Mechanical residual strength
|
kN
|
32
|
|
Diameter of the insulating part
|
mm
|
175
|
|
Spacing
|
mm
|
110
|
|
Nominal creepage distance
|
mm
|
300
|
|
Ball and socket coupling
|
mm
|
11
|
|
Puncture voltage in insulating medium
|
kV
|
100
|
|
50 Hz withstand voltage (dry)
|
kV
|
60
|
|
50 Hz withstand voltage (wet)
|
kV
|
34
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
85/85
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
60
|
|
kV
|
20
|
|
dB
|
86
|
|
kV
|
25
|
|
Weight
|
kg
|
2,5
|
|
|
|
|
|
HV glass suspension insulator U 300BP
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
Designation
|
IEC 305
|
U 300ÂÐ
|
|
|
GOST 27661
|
ÏÑÂ 300À
|
ÏÑÂ 300À
|
|
Mechanical failing load
|
kN
|
300
|
300
|
|
Mechanical residual strength
|
kN
|
240
|
240
|
|
Diameter of the insulating part
|
mm
|
360
|
360
|
|
Spacing
|
mm
|
195
|
198
|
|
Nominal creepage distance
|
mm
|
617
|
617
|
|
Ball and socket coupling
|
mm
|
24
|
24
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
100
|
100
|
|
50 Hz withstand voltage (wet)
|
kV
|
60
|
60
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
155/155
|
155/155
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
86
|
86
|
|
kV
|
60
|
60
|
|
Weight
|
kg
|
13,3
|
13,3
|
|
|
|
|
|
HV glass suspension insulator U 160BSP, U 160BLP
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
Designation
|
IEC 305
|
U 160BSP
|
U 160BLP
|
|
GOST 27661
|
ÏÑB 160A
|
ÏÑB 160A
|
|
Mechanical failing load
|
kN
|
160
|
160
|
|
Mechanical residual strength
|
kN
|
128
|
128
|
|
Diameter of the insulating part
|
mm
|
320
|
320
|
|
Spacing
|
mm
|
146
|
170
|
|
Nominal creepage distance
|
mm
|
545
|
545
|
|
Ball and socket coupling
|
mm
|
20
|
20
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
90
|
90
|
|
50 Hz withstand voltage (wet)
|
kV
|
55
|
55
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
140/140
|
140/140
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
60
|
60
|
|
kV
|
20
|
20
|
|
dB
|
86
|
86
|
|
kV
|
35
|
35
|
|
Weight
|
kg
|
8,28
|
8,28
|
|
|
|
|
|
HV glass suspension insulator U 125BP
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
Designation
|
IEC 305
|
U125BP
|
|
Mechanical failing load
|
kN
|
125
|
|
Mechanical residual strength
|
kN
|
100
|
|
Diameter of the insulating part
|
mm
|
280
|
|
Spacing
|
mm
|
146
|
|
Nominal creepage distance
|
mm
|
445
|
|
Ball and socket coupling
|
mm
|
20
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
82
|
|
50 Hz withstand voltage (wet)
|
kV
|
50
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
125/125
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
86
|
|
kV
|
30
|
|
Weight
|
kg
|
5,86
|
|
|
|
|
|
HV glass suspension insulator U 120BP
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
LIC.Ltd
|
|
Designation
|
IEC 305
|
|
U120ÂÐ
|
|
ÐSV120Â
|
|
GOST 27661
|
ÏÑÂ120Á
|
ÏÑÂ120Á
|
ÏÑÂ120Á
|
ÏÑÂ120Á
|
|
Mechanical failing load
|
kN
|
120
|
120
|
120
|
120
|
|
Mechanical residual strength
|
kN
|
96
|
96
|
96
|
96
|
|
Diameter of the insulating part
|
mm
|
280
|
280
|
290
|
290
|
|
Spacing
|
mm
|
127
|
146
|
146
|
146
|
|
Nominal creepage distance
|
mm
|
445
|
445
|
442
|
442
|
|
Ball and socket coupling
|
mm
|
16
|
16
|
16
|
16
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
130
|
130
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
82
|
82
|
82
|
82
|
|
50 Hz withstand voltage (wet)
|
kV
|
50
|
50
|
50
|
50
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
125/125
|
125/125
|
125/125
|
125/125
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
60
|
60
|
60
|
60
|
|
kV
|
20
|
20
|
20
|
20
|
|
dB
|
86
|
86
|
86
|
86
|
|
kV
|
30
|
30
|
30
|
| | | | |