Catalog
|
HV glass suspension insulator U 300Â
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
LIC.Ltd
|
|
Designation
|
IEC 305
|
U 300Â
|
U 300B
|
U 300Â
|
|
GOST 27661
|
ÏÑ 300Â
|
ÏÑ 300Ã
|
ÏÑ 300Â
|
|
Mechanical failing load
|
kN
|
300
|
300
|
300
|
|
Mechanical residual strength
|
kN
|
240
|
240
|
240
|
|
Diameter of the insulating part
|
mm
|
320
|
320
|
320
|
|
Spacing
|
mm
|
195
|
195
|
195
|
|
Nominal creepage distance
|
mm
|
390
|
485
|
385
|
|
Ball and socket coupling
|
mm
|
24
|
24
|
24
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
130
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
82
|
82
|
82
|
|
50 Hz withstand voltage (wet)
|
kV
|
50
|
50
|
50
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
130/130
|
130/130
|
130/130
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
60
|
34
|
60
|
|
kV
|
20
|
10
|
20
|
|
dB
|
86
|
86
|
86
|
|
kV
|
40
|
40
|
40
|
|
Weight
|
kg
|
10,0
|
11,5
|
10,0
|
|
|
|
|
|
HV glass suspension insulator U 40B
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
LIC.Ltd
|
|
Designation
|
IEC 305
|
|
U 40Â
|
U 40Â
|
|
GOST 27661
|
ÏÑ 40À
|
ÏÑ 40À
|
ÏÑ 40
|
|
Mechanical failing load
|
kN
|
40
|
40
|
40
|
|
Mechanical residual strength
|
kN
|
32
|
32
|
32
|
|
Diameter of the insulating part
|
mm
|
175
|
175
|
175
|
|
Spacing
|
mm
|
100
|
110
|
110
|
|
Nominal creepage distance
|
mm
|
190
|
190
|
185
|
|
Ball and socket coupling
|
mm
|
11
|
11
|
11
|
|
Puncture voltage in insulating medium
|
kV
|
100
|
100
|
100
|
|
50 Hz withstand voltage (dry)
|
kV
|
55
|
55
|
55
|
|
50 Hz withstand voltage (wet)
|
kV
|
33
|
33
|
30
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
70/70
|
70/70
|
70/70
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
86
|
86
|
86
|
|
kV
|
25
|
25
|
25
|
|
Weight
|
kg
|
1,7
|
1,7
|
1,7
|
|
|
|
|
|
HV glass suspension insulator U125B
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
|
Designation
|
IEC 305
|
U125B
|
|
Mechanical failing load
|
kN
|
125
|
|
Mechanical residual strength
|
kN
|
100
|
|
Diameter of the insulating part
|
mm
|
255
|
|
Spacing
|
mm
|
146
|
|
Nominal creepage distance
|
mm
|
320
|
|
Ball and socket coupling
|
mm
|
20
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
70
|
|
50 Hz withstand voltage (wet)
|
kV
|
40
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
kV
|
100/100
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
86
|
|
kV
|
30
|
|
Weight
|
kg
|
4,1
|
|
|
|
|
|
HV glass suspension insulator U210Â
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
LIC.Ltd
|
|
Designation
|
IEC 305
|
U 210Â
|
|
U 210Â
|
|
GOST 27661
|
ÏÑ 210Â
|
ÏÑ 210Â
|
ÏÑ 210Â
|
|
Mechanical failing load
|
kN
|
210
|
210
|
210
|
|
Mechanical residual strength
|
kN
|
168
|
168
|
168
|
|
Diameter of the insulating part
|
mm
|
290
|
290
|
300
|
|
Spacing
|
mm
|
170
|
195
|
170
|
|
Nominal creepage distance
|
mm
|
380
|
380
|
370
|
|
Ball and socket coupling
|
mm
|
20
|
20
|
20
|
|
Puncture voltage in insulating medium
|
kV
|
130
|
130
|
130
|
|
50 Hz withstand voltage (dry)
|
kV
|
72
|
72
|
72
|
|
50 Hz withstand voltage (wet)
|
kV
|
45
|
45
|
45
|
|
Dry lightning impulse withstand voltage 1.2/50+/- one unit
|
êÂ
|
110/110
|
110/110
|
110/110
|
|
Radio interference voltage at 0.5 MHz
|
dB
|
60
|
60
|
60
|
|
kV
|
20
|
20
|
20
|
|
dB
|
86
|
86
|
86
|
|
kV
|
40
|
40
|
40
|
|
Weight
|
kg
|
7,2
|
7,2
|
7,1
|
|
|
|
|
|
HV glass suspension insulator U 120B
|
|
|
Manufacturer
|
JSC “YuAIZ”
|
LIC.Ltd
|
|
Designation
|
IEC 305
|
|
U120Â
|
U120Â
|
|
GOST 27661
|
ÏÑ120Á
|
ÏÑ120Á
|
ÏÑ120Á
|
|
Mechanical failing load
|
kN
|
120
|
120
|
120
|
|
Mechanical residual strength
|
kN
|
96
|
96
|
96
|
|
Diameter of the insulating part
|
mm
|
255
|
| | | | |