Catalog
|
SHF 10 G
|
Insulator unit of this type comlies with Specs (TU) 3493-133-00111120-96 requirements. |
|
Minimum voltage
|
Puncture voltage in insulating medium |
kV
|
160
|
| Impulse withstand voltage |
kV
|
100
|
| 50 Hz withstand voltage (Dry) |
kV
|
65
|
| 50 Hz withstand voltage (Wet) |
kV
|
42
|
| Average annual rate of failure |
failures/year
|
0.0007
|
| Creepage distance, minimum |
mm
|
256
|
| Mechanical failing load (bending), minimum |
kN
|
12.5
|
| Weight, maximum |
kg
|
1.9
|
|
|
|
|
|
SHF 20G
|
Insulator unit of this type complies with Specs (TU) 3493-170-00111120-2000 requirements. |
|
Minimum voltage
|
Puncture voltage in insulating medium |
kV
|
180
|
| Impulse withstand voltage |
kV
|
135
|
| 50 Hz withstand voltage (Dry) |
kV
|
85
|
| 50 Hz withstand voltage (Wet) |
kV
|
65
|
| Average annual rate of failure |
failure/year
|
0.0005
|
| Creepage distance, minimum |
mm
|
400
|
| Mechanical failing load (beding), minimum |
kN
|
13
|
| Weight, maximum |
kg
|
3.5
|
|
|
|
|
|
SHF 20G 1
|
|
Minimum voltage |
Puncture voltage in insulating medium |
kV |
180 |
| Impulse withstand voltage |
kV |
135 |
| 50 Hz withstand voltage (Dry) |
kV |
85 |
| 50 Hz withstand voltage (Wet) |
kV |
65 |
| Creepage distance, minimum |
mm |
400 |
| Mechanical failing load (beding), minimum |
kN |
13 |
| Weight, maximum |
kg |
3.5 |
|
|
|
|
|
|
|
 |